Home / Resources / Steel Building Design Codes
Steel Building Design Codes by Country: A 2026 Cross-Reference
A pre-engineered steel building package usually crosses two code regimes at once: the standard the buyer’s engineer of record designs to, and the standard the fabrication shop works to. This reference maps the governing steel building design codes across 13 markets, then cross-maps the four areas that actually cause submittal rejections — material grades, execution classes, bolting systems and corrosion protection.
How to read this reference
Three different parties own three different documents on a single PEB order. The engineer of record selects the design and loading codes and seals the calculations. The fabricator works to a welding and execution standard. The third-party inspector applies an acceptance criteria that may come from a fourth document entirely. Any steel building design codes table that lists only the member check therefore answers a third of the question.
For example, a warehouse in Jazan may be designed to SBC 301 loads and SBC 306 member checks, fabricated under EN 1090-2 execution class EXC2, welded to ISO 3834-2 quality requirements, and inspected against EN ISO 5817 level C. Four standards, one building. None of them is optional, and none of them substitutes for another.
Steel building design codes by country
| Market | Structural steel design | Loading | Cold-formed steel | Seismic |
|---|---|---|---|---|
| United States | AISC 360-22; AISC 303-22 for standard practice; MBMA Metal Building Systems Manual (2024 ed.) for PEMB systems | ASCE 7-22; IBC 2024 | AISI S100-16 (R2020); AISI S240-20 | ASCE 7-22 Chapters 11–23 |
| Canada | CSA S16:24 | NBCC 2020, Part 4 | CSA S136 (AISI S100 harmonised) | NBCC 2020, Part 4 |
| Mexico | NTC-Metálicas (current CDMX edition); AISC 360 on industrial projects | NTC-Cargas | AISI S100 | NTC-Sismo |
| European Union | EN 1993-1-1 with the relevant National Annex | EN 1991-1-1 to 1-4 | EN 1993-1-3 | EN 1998-1 |
| United Kingdom | BS EN 1993-1-1 + UK National Annex; BS 5950 retained for existing structures | BS EN 1991 | BS EN 1993-1-3 | BS EN 1998-1 + UK NA |
| China | GB 50017-2017 | GB 50009-2012 | GB 50018-2002 | GB 50011-2010 (2016 amendment) |
| India | IS 800:2007 | IS 875, Parts 1–5 | IS 801:1975 | IS 1893 (Part 1):2016 |
| Australia / New Zealand | AS 4100:2020 | AS/NZS 1170.0 to 1170.3 | AS/NZS 4600:2018 | AS 1170.4, NZS 1170.5 |
| Brazil | ABNT NBR 8800:2008 | ABNT NBR 8681:2003 | ABNT NBR 14762:2010 | ABNT NBR 15421:2006 |
| Indonesia | SNI 1729:2020 | SNI 1727:2020 | SNI 7971:2013 | SNI 1726:2019 |
| Philippines | NSCP 2015, Vol. 1 (AISC 360-10 basis) | NSCP 2015 | NSCP 2015 / AISI S100 | NSCP 2015 |
| Saudi Arabia | SBC 306 (2018), AISC 360 basis | SBC 301 (2018), ASCE 7-16 basis | AISI S100 | SBC 301 (2018) |
| South Africa | SANS 10162-1:2011 | SANS 10160 series | SANS 10162-2 | SANS 10160 series |
Three families of design philosophy
Most cross-border disputes trace back to one fact: the same member produces a different utilisation ratio under AISC, Eurocode and GB. AISC 360 uses nominal strength multiplied by a resistance factor φ. Eurocode 3 uses characteristic resistance divided by a partial factor γM. GB 50017 uses design values with its own partial factors. The target reliability indices behind those numbers are not identical, and the load factors feeding them differ too.
Consequently, a member designed to 95% utilisation under AISC 360 will usually not pass a Eurocode check unchanged, and a GB-optimised section will look over-designed to an ASCE 7 reviewer. The correct response is to re-run the member checks in the nominated code, not to convert the final number with a factor.
Steel grade cross-reference
| Grade | Standard | Yield fy (MPa, t ≤ 16 mm) | Tensile fu (MPa) |
|---|---|---|---|
| A36 | ASTM A36/A36M | 250 | 400–550 |
| A992 | ASTM A992/A992M | 345–450 | 450 min. |
| A572 Gr. 50 | ASTM A572/A572M | 345 | 450 min. |
| S235JR / J0 / J2 | EN 10025-2 | 235 | 360–510 |
| S275JR / J0 / J2 | EN 10025-2 | 275 | 430–580 |
| S355JR / J0 / J2 / ML | EN 10025-2 | 355 | 470–630 |
| S420ML | EN 10025-2 / -4 | 420 | 500–660 |
| Q235B | GB/T 700 | 235 | 370–500 |
| Q355B / Q355D | GB/T 1591 | 355 | 470–630 |
| E250 (Fe 410W) | IS 2062 | 250 | 410 min. |
| E350 (Fe 490W) | IS 2062 | 350 | 490 min. |
| Grade 300 | AS/NZS 3679.1 | 300 | 440 |
| Grade 350 | AS/NZS 3679.1 | 330–340 (by thickness) | 450 |
| SS400 | JIS G3101 | 245 | 400–510 |
| SN400B | JIS G3136 | 235 | 400–510 |
Rules for substituting one grade for another
- Yield strength is thickness-dependent. EN 10025 drops fy above 16 mm and again above 40 mm. Quoting 355 MPa for a 30 mm end plate on a European plate is wrong by roughly 10%. Check the thickness band before you release the BOM.
- A992 has no direct overseas equivalent. It is a US wide-flange-specific specification with a minimum fy/fu ratio requirement that makes it weldable and ductile. Outside North America the usual substitutes are S355J2 or A572 Gr. 50, and both need an explicit equivalence note in the submittal.
- Impact toughness is a separate purchase condition. The JR / J0 / J2 suffix is the Charpy designation, tested at +20 °C, 0 °C and −20 °C respectively. Cold-store or high-altitude projects routinely need J2 or ML. A grade certificate without the impact line is not a certificate of conformity.
- Mill certificates must state the standard and the heat number. For structural steel in a CE-marked package, that means an inspection certificate to EN 10204 3.1, issued by the mill rather than the stockholder.
Execution and weld quality frameworks
This is where most overseas submittals fail. Each region regulates fabrication through a different concept, so a package built for one reviewer looks incomplete to another. The four frameworks below are not translations of one another; they attach responsibility differently.
| Framework | Applies in | How it classifies the work | Weld acceptance | Default NDT expectation |
|---|---|---|---|---|
| AWS D1.1/D1.1M:2020 | US, and contract-based projects elsewhere | Statically or cyclically loaded; fracture-critical member (FCM) status assigned by the engineer | Visual plus ultrasonic, acceptance by clause 6 | 100% UT on complete-joint-penetration groove welds in FCM; visual on all welds |
| AISC 360-22 Ch. N + AISC 303-22 | US | Splits quality assurance from quality control between EOR, fabricator and erector | Refers to AWS D1.1 | Fabricator holds an approved QC programme; AISC certification is voluntary but commonly specified |
| EN 1090-1 + EN 1090-2:2018 | EU, UK, and adopted widely in the Gulf and North Africa | Execution classes EXC1 to EXC4, derived from consequence class, service category and production category | EN ISO 5817 quality levels B, C or D | Percentage NDT rises with execution class and weld type; EXC3 and EXC4 approach full inspection on butt welds |
| GB 50205-2020 + GB 50661-2011 | China, and Chinese-funded projects abroad | Weld quality grades 一级, 二级, 三级 (Grade I, II, III) | Ultrasonic testing to GB/T 11345 | Grade I butt welds in tension are inspected at 100%; Grade II at 20% |
| AS/NZS 5131:2016 | Australia, New Zealand | Construction categories CC1 to CC4 | AS/NZS 1554 series | Inspection scope scales with construction category |
What each framework actually asks you to submit
The documentation set is more standardised than the classification systems suggest. In practice a reviewer in any of these jurisdictions wants the same six things, and only the form numbers change.
- Welding procedure specification and its supporting procedure qualification record — ISO 15614-1 for European work, AWS D1.1 clause 4 for US work. A WPS without a matching PQR is a template, not a qualification.
- Welder qualification certificates — ISO 9606-1 or AWS D1.1 clause 4 part C, with the process, position and thickness range each welder is qualified for. A certificate naming only the process is insufficient.
- Consumable certificates and the storage record for low-hydrogen electrodes. Reviewers in humid climates ask for the drying log.
- NDT reports with the technician’s Level II certification, the procedure reference and the acceptance level applied.
- Dimensional and trial assembly report for any truss or frame that will not fit in a container without being split.
- Coating records — surface preparation grade, dry film thickness readings by member, and the batch certificates for the paint system.
Structural bolting systems
| System | Standard | Grades | What the inspector checks |
|---|---|---|---|
| US high-strength bolts | ASTM F3125/F3125M | Gr. A325, Gr. A490, Gr. F1852 twist-off | RCSC Specification (2020): snug-tight, pretensioned or slip-critical; turn-of-nut or direct tension indicator |
| European preloaded bolts | EN 14399-3 (HR) and EN 14399-4 (HV) | 8.8 and 10.9 | EN 1090-2 clause 8: tightening method, k-class, calibrated wrench or torque wrench with daily verification |
| European non-preloaded bolts | EN 15048-1 | 8.8, 10.9 | Bearing connections only; not permitted where the design assumes preload |
| Chinese high-strength bolts | GB/T 1228 to GB/T 1231 | 8.8S and 10.9S | Torque coefficient test per batch; GB 50205-2020 for the site inspection record |
| Australian high-strength bolts | AS/NZS 1252.1 | 8.8, 10.9 | Property class marking plus assembly verification testing |
Four bolting traps in cross-code procurement
F3125 is not a new bolt. ASTM consolidated A325 and A490 into F3125 in 2016. A specification that still calls for A325 is satisfied by F3125 Gr. A325, but a submittal that lists only “A325” with no standard reference will be returned by a careful reviewer. Write both.
Thread form cannot be mixed. Unified inch threads and metric coarse threads are not interchangeable, and a galvanized assembly adds a further clearance allowance. If a US-designed frame is fabricated in China, the bolt hole diameters, the bolt lengths and the spanner sizes all change. Fix the thread standard in the order documents.
Galvanizing and slip-critical joints conflict. Hot-dip galvanized faying surfaces default to a lower slip factor unless the fabricator either roughens them or supplies tested class B surfaces. Painting the faying surface is generally prohibited. Confirm the slip factor in the design before the galvanizer loads the kettle.
Torque is not a universal number. A tightening torque derived from a k-factor of 0.13 will over-tension a batch with a tested coefficient of 0.11. Chinese 10.9S bolts ship with a batch torque coefficient certificate, and the site torque must be recalculated from it rather than copied from a table.
Corrosion protection and galvanizing
| Reference | Defines | Values worth memorising |
|---|---|---|
| ISO 12944-2:2017 | Atmospheric corrosivity categories and durability bands | C1 to C5, plus CX for offshore; durability low, medium, high and very high |
| ISO 1461 | Hot-dip galvanized coating on fabricated steel | Minimum total coating mass 610 g/m² (about 85 µm) on steel 6 mm and thicker; lower masses permitted on thinner sections |
| ASTM A123/A123M | Zinc coating on iron and steel products | 2.0 oz/ft² (610 g/m²) on steel 3/16 in (4.8 mm) and thicker |
| ASTM A653/A653M | Zinc-coated sheet steel | G90 equals 0.90 oz/ft² total, approximately Z275; G60 approximately Z180 |
| ASTM A792/A792M | Aluminium-zinc coated sheet | AZ50 and AZ55, the usual substrate for 55% Al-Zn roof and wall panels |
Three practical rules follow. First, specify the corrosivity category, not the coating thickness, then let the coating thickness follow from ISO 12944-5. Second, treat cut edges, weld spatter and site-drilled holes as coating defects that need a zinc-rich repair coat, because no shop system survives an untreated edge in a C4 environment. Third, for coastal and marine sites use a duplex system — galvanizing plus a topcoat — since the paint alone will not hold at C5-M and the galvanizing alone will not hold its appearance.
Coating thickness is specified, not assumed: the same galvanized frame can be held to 55 µm, 65 µm or 63 µm depending on whether the order cites ISO 1461, ASTM A123 or JIS H 8641. Our companion reference sets the five galvanizing standards side by side, converts coating mass to thickness, and works the service-life arithmetic for each ISO 12944 corrosivity category: galvanizing coating thickness by standard.
What an approval package should contain
| Document | Purpose | Common omission |
|---|---|---|
| Design basis statement | Names every code, edition, national annex, and the load cases used | Edition year left out, so the reviewer assumes the current one |
| Member and connection calculations | Demonstrates utilisation in the nominated code | Connection design skipped on the assumption that the supplier’s standard detail governs |
| Material certificates | Proves grade, heat number and impact toughness | Stockholder certificate submitted instead of a mill 3.1 certificate |
| WPS and PQR set | Proves the welding procedure is qualified | PQR written for a different thickness range than the actual plates |
| Welder and NDT operator certificates | Proves personnel qualification and scope | Certificates valid but outside the position or thickness range used |
| Coating specification and DFT record | Proves the system meets the corrosivity category | Only the shop primer is recorded; the finish coat is applied on site with no record |
| Erection drawings and anchor bolt plan | Coordinates the foundation interface | Anchor rod projection given without tolerance, causing site collisions |
| Packing list by mark | Allows site receipt checking against the erection sequence | Marks not matched to erection drawings, so the site opens every bundle |
Seven mistakes that get a PEB submittal rejected
- Porting a design across codes. A member checked to AISC 360 and re-issued under EN 1993 without a re-check is the single most common technical objection raised against imported packages.
- Sending a GB 50205 weld package to an AISC reviewer. The documentation is real, but the reviewer has no basis to accept Grade I as equivalent to fracture-critical inspection. Map the acceptance criteria explicitly.
- Listing A325 in a bill of materials. The current standard is ASTM F3125. Omitting it looks like an outdated supply chain.
- Preloaded joints on galvanized members with no slip factor. The design assumes class A and the surface delivers less, so the connection is under-designed before it is built.
- Quoting galvanizing in microns against a specification in ounces per square foot. Both are legitimate; mixing them across a submittal and a purchase order is how a batch gets rejected at the galvanizer.
- Designing purlins to AISI S100 but loading them with Eurocode snow drift. The member standard and the load standard must come from the same regime, or the drift case must be converted with a stated basis.
- No trial assembly for long-span trusses. A 40 m truss that was never trial-assembled will find its mismatch on site, in the air, on a crane clock.
Need a package that survives a foreign reviewer?
SynJect fabricates to the code your engineer of record nominates rather than to a single house standard. We routinely deliver to AISC 360, EN 1090-2 execution classes up to EXC3, GB 50205 and AS/NZS 5131 projects, with the WPS, PQR, welder certificates and mill certificates issued in the format the reviewer expects.
Two starting points: our fabrication capabilities and the certificate register. For a specific project, send the design basis and we will return a code-compliance note with the quotation.
Where to obtain the current text of each steel building design code
Working from a second-hand copy of a standard is how edition errors enter a project. These are the issuing bodies that publish and sell the documents in the table above, plus the two international bodies behind the welding and corrosion references.
| Issuing body | Covers | Publisher |
|---|---|---|
| AISC and ASCE | United States: AISC 360, AISC 303, ASCE 7 | aisc.org |
| CSA Group | Canada: CSA S16, CSA S136 | csagroup.org |
| CEN | European Union: EN 1993, EN 1991, EN 1090 | cencenelec.eu |
| BSI | United Kingdom: BS EN adoptions and UK National Annexes | bsigroup.com |
| SAC and SAMR | China: GB 50017, GB 50205, GB 50661 | sac.gov.cn |
| Bureau of Indian Standards | India: IS 800, IS 875, IS 801 | bis.gov.in |
| Standards Australia | Australia and New Zealand: AS 4100, AS/NZS 1170, AS/NZS 5131 | standards.org.au |
| ABNT | Brazil: NBR 8800, NBR 14762 | abnt.org.br |
| ISO and ASTM | Welding quality, galvanizing, corrosivity and bolt specifications | iso.org, astm.org |
Keeping this reference current
Three of the documents above move on fixed cycles worth diarising. ASCE 7 and the IBC publish on a three-year cycle, and the MBMA manual follows the IBC, so a US package specified in 2026 will be reviewed against ASCE 7-22 and IBC 2024 until the next editions land. Eurocode 3 is mid-transition to its second generation, which means a project specified today may be checked against EN 1993-1-1 as amended by the second generation part if the National Annex has been updated. CSA S16 moved to the 2024 edition, superseding S16:19.
If you are specifying steel building design codes across more than one market, the practical rule is to write the edition year into the design basis statement and into the purchase order. A clause that says “AISC 360” invites a reviewer to assume the newest edition; a clause that says “AISC 360-22” does not. The same discipline applies to the material and execution standards that hang off the design code, which is why the reference above lists them together rather than as separate families.
Sources and scope
Compiled by the SynJect engineering team from publisher catalogues and standards bodies: AISC, ASCE, ICC, CSA Group, CEN, BSI, SAC, Standards Australia, ABNT, BSN, NSCP, the Saudi Building Code National Committee, SABS, ISO, ASTM and MBMA. This steel building design codes reference covers building structures only; it excludes bridges, cranes, offshore structures, pressure vessels and storage tanks, each of which has its own governing standard. Nothing here replaces the engineer of record’s judgement or the authority having jurisdiction’s written direction.